Xinzheng Industrial Park,Qingyuan West Street,Weifang Economic Development Zone,Shandong,China
diesel generator  +86 15905360231    diesel generator  huaquan@huaquanpower.com
CURRENT LOCATION:HOME > generator 400kw > Generating units should have the following automatic index >
Generating units should have the following automatic index
Update:2017-02-18 Tags:automatically

1.the city power generator price

outages, missing phase and voltage exceeds 380 v (15-10%), or ground remote control switch, the unit should be able to automatically start, start the cycle by three times, each time you start time: 10 s, start the interval of not less than 30 seconds, from total time does not exceed 120, start-up success rate should be greater than 99%.

2, automatic switch, uninstall the city electricity blackouts, unit since the successful start automatically switches to the main power supply unit load, if the host fault, automatic switch to the standby power supply unit. City is back to normal, the power supply automatically fall into the city, and then the unit automatically delay automatically postponed for 3 to 5 minutes.

3, unit the following failure, automatic shutdown protection unit, and send a signal.